* Dantherm A/S, Skive, 7800 DENMARK Controller - CC6 BL.Ver - 0.6 App.Ver - 0.96 Gfx.Ver - 0.0 Date - 19/10/2023 Time - 09.42 Serial No. - 1844071794 ------------------------------------------------------------- Device Name - CDP ------------------------------------------------------------- ------------------------------------------------------------- [EC Configuration] Drive 1 Drive 2 Drive 3 1.Low OFF [fP0][float]: 0.0 :0.0 :0.0 2.Low ON [fP1][float]: 0.0 :0.0 :0.0 3.P-band start [fP2][float]: 0.0 :0.0 :0.0 4.P-band stop [fP4][float]: 0.0 :0.0 :0.0 5.High OFF [fP5][float]: 0.0 :0.0 :0.0 6.High ON [fP6][float]: 0.0 :0.0 :0.0 7.Low_RPM [fR0][0-9999]: 1000 :0 :0 8.High RPM [cR2][0-9999]: 1500 :0 :0 9.Low Duty Cycle [xD1][0-100]: 8 :0 :0 10.HIGH Duty Cycle [xD2][0-100]: 100 :0 :0 11.Dead Band RPM [xDb][100-1000]: 200 :0 :0 12.Override - Digi.1 [x/0-100]: x :0 :0 13.Override - Digi.2 [x/0-100]: x :0 :0 14.Override - Digi.3 [x/0-100]: x :0 :0 15.Override - Digi.4 [x/0-100]: x :0 :0 16.Override - Digi.5 [x/0-100]: x :0 :0 17.Override - Sensor Fail [x/0-100]: x :0 :0 18.Sens.Sel. [0-7]: 0 :0 :0 19.Tacho pulse/rev [0-10]: 0 :0 :0 20.Min. ON duration Sec. [0-3600]: 0 :0 :0 21.Restart time-out Sec. [0-3600]: 0 :0 :0 22.Enable [0/1]: 1 :0 :0 > Sensors Select -> T1/T2/T3/T4/BUS1/BUS2/App.Specific ------------------------------------------------------------- [Relay(On/Off) Drive Compressor Configuration] Drive 1 Drive 2 Drive 3 Drive 4 Drive 5 Drive 6 Drive 7 1.Low OFF [cP0][float]: 0.0 :0.0 :0.0 :28.0 :0.0 :-49.0 :0.0 2.Low ON [cP1][float]: 0.0 :0.0 :0.0 :31.0 :0.0 :-49.0 :0.0 3.High ON [cP0][float]: 0.0 :0.0 :0.0 :31.0 :0.0 :26.0 :0.0 4.High OFF [cP1][float]: 0.0 :0.0 :0.0 :31.0 :0.0 :28.0 :0.0 5.Override - Digi.1 [x/0/1]: x :x :x :x :x :0 :0 6.Override - Digi.2 [x/0/1]: x :x :x :x :x :0 :0 7.Override - Digi.3 [x/0/1]: x :x :x :x :x :0 :0 8.Override - Digi.4 [x/0/1]: x :x :x :x :x :0 :0 9.Override - Digi.5 [x/0/1]: x :x :x :x :x :0 :0 10.Override - Sensor Fail [x/0/1]: x :x :x :x :x :0 :0 11.Sens.Sel. [0-7]: 6 :6 :6 :6 :6 :6 :0 12.Min. ON duration Sec. [0-3600]: 360 :0 :0 :0 :0 :0 :0 13.Restart time-out Sec. [0-3600]: 240 :0 :0 :0 :0 :0 :0 14.Enable [0/1]: 1 :1 :1 :1 :1 :1 :0 > Sensors Select -> T1/T2/T3/T4/BUS1/BUS2/App.Specific ------------------------------------------------------------- [Night Program Configuration] 1.Start Time [hh/mm]: 22/0 2.End Time [hh/mm]: 08/0 3.Manual Duration(Hours) [0-12]: 8 4.Enable [0/1]: 0 ------------------------------------------------------------- [Communication Configuration] 1.RF address [32bit]: 123456789 2.RF [868MHz] channel [1-4]: 2 3.RF enable [0/1]: 1 4.RS-485 Bus Pow. [MBpow][0/1]: 0 5.ModBus baudrate [9600/14400/19200]: 9600 6.ModBus aAddr [MBaddr][1-247]: 2 ------------------------------------------------------------- [System Control Configuration] 1.Controller Type [CCT][10x/20x/30x/40x]: 301 2.Volt. Sens. Enable [Vena][0/1]: 0 3.Curr. sens. Enable [Iena][0/1]: 0 4.V - Low Limit [Vl][0-300]: 0 5.V - High Limit [Vm][0-300]: 0 6.I - Low Limit [Il][1-10]: -1 7.I - High Limit [Im][1-10]: -1 8.Temp Low Limit [float]: 0 9.Temp High Limit 1 [float]: 39 10.Temp High Limit 2 [float]: 39 11.Temp Limit Hyst. [float]: 2 12.Status Log Dis/Ena. [0/1]: 1 13.Log interval in min. [1-60]: 1 14.Energy meter puls/Kwh [0-2000]: 1000 15.Alarm1 NO/NC Type [0/1]: 0 16.Alarm2 NO/NC Type [0/1]: 0 17.Alarm3 NO/NC Type [0/1]: 0 18.Alarm4 NO/NC Type [0/1]: 0 19.Alarm1 delay sec [0-100]: 0 20.Alarm2 delay sec [0-100]: 0 21.Alarm3 delay sec [0-100]: 0 22.Alarm4 delay sec [0-100]: 0 23.Dig.1 NO/NC Type [0/1]: 0 24.Dig.2 NO/NC Type [0/1]: 0 25.Dig.3 NO/NC Type [0/1]: 0 26.Dig.4 NO/NC Type [0/1]: 0 27.Dig.5 NO/NC Type [0/1]: 0 28.Dig.6 NO/NC Type [0/1]: 0 29.Language sel [0-25]: 0 30.Image Rotation Up/Down [0-1]: 1 Controller type >> 1xx - Aerial 2xx - Calorex 3xx - Dantherm 4xx - Master Controller type >> xx - (00/01/02/03/04/06) -> (None/CD/AD/HP/AC/Vent) ------------------------------------------------------------- [Alarm Mapping Configuration] Error <-> Alarm | 1 | 2 | 3 | 4 | 1.Voltage Low [VL]: 0 :0 :0 :0 2.Voltage High [VH]: 0 :0 :0 :0 3.Current Low [CL]: 0 :0 :0 :0 4.Current High [CH]: 0 :0 :0 :0 5.T1 [FG]: 0 :0 :0 :0 6.T2 [PI]: 0 :0 :0 :0 7.T3 [PI]: 0 :0 :0 :0 8.T4 [PI]: 0 :0 :0 :0 9.Rh 1 : 0 :0 :0 :0 10.VOC 1 : 0 :0 :0 :0 11.Co2 1 : 0 :0 :0 :0 12.Flow 1 : 0 :0 :0 :0 13.Rh 2 : 0 :0 :0 :0 14.VOC 2 : 0 :0 :0 :0 15.Co2 2 : 0 :0 :0 :0 16.Flow 2 : 0 :0 :0 :0 17.Dig 1 I/P [AS]: 0 :0 :0 :0 18.Dig 2 I/P [SS]: 0 :0 :0 :0 19.Dig 3 I/P [CS]: 0 :0 :0 :0 20.Dig 4 I/P [AS]: 0 :0 :0 :0 21.Dig 5 I/P [SS]: 0 :0 :0 :0 22.Dig 6 I/P [CS]: 0 :0 :0 :0 23.EC Drive 1 [D1]: 0 :0 :0 :0 24.EC Drive 2 [D1]: 0 :0 :0 :0 25.EC Drive 3 [D1]: 0 :0 :0 :0 26.Tempr Low [F1]: 0 :0 :0 :0 27.Tempr Limit 1 [F2]: 0 :0 :0 :0 28.Tempr Limit 2 [F3]: 0 :0 :0 :0 29.Humid. Low [RS]: 0 :0 :0 :0 30.Humid. High [AS]: 0 :0 :0 :0 31.VOC Limit [CS]: 0 :0 :0 :0 32.CO2 Limit [CS]: 0 :0 :0 :0 33.Fltr Pressure 1 [SS]: 0 :0 :0 :0 34.Fltr Pressure 2 [CS]: 0 :0 :0 :0 35.Exp. Valve [EXV]: 0 :0 :0 :0 36.RF [DX]: 0 :0 :0 :0 37.Intern. memory [HP]: 0 :0 :0 :0 38.SD Card [LP]: 0 :0 :0 :0 39.HP_ERROR [ ]: 0 :0 :0 :0 40.LP_ERROR [ ]: 0 :0 :0 :0 41.sys. Active [ ]: 0 :0 :0 :0 42.Prod. Err 1 [ ]: 0 :0 :0 :0 43.Prod. Err 2 [ ]: 0 :0 :0 :0 44.Prod. Err 3 [ ]: 0 :0 :0 :0 45.Prod. Err 4 [ ]: 0 :0 :0 :0 ------------------------------------------------------------- [Component Select Mapping Configuration] Component <-> Drive | EC-1 | EC-2 | EC-3 | Rly-1 | Rly-2 | Rly-3 | Rly-4 | Rly-5 | Rly-6 | Rly-7 | | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 1.Fan 1 : 1 : 0 : 0 : 0 : 1 : 0 : 0 : 0 : 0 : 0 2.Fan 2 : 0 : 0 : 0 : 0 : 0 : 0 : 0 : 0 : 0 : 0 3.Compressor/Motor : 0 : 0 : 0 : 1 : 0 : 0 : 0 : 0 : 0 : 0 4.Damper : 0 : 0 : 0 : 0 : 0 : 0 : 0 : 1 : 0 : 0 5.Heater : 0 : 0 : 0 : 0 : 0 : 0 : 0 : 0 : 1 : 0 6.Valve : 0 : 0 : 0 : 0 : 0 : 1 : 0 : 0 : 0 : 0 7.Pump/Aux : 0 : 0 : 0 : 0 : 0 : 0 : 1 : 0 : 0 : 0 ------------------------------------------------------------- [Other Settings] 1.Device Name : CDP 2.Password : 1234 3.Service interval : 1000 4.Service note ena : 0 ------------------------------------------------------------- [Product Configuration - Cond. Dehumidifier] 1.Start Delay Fan sec. [0-1800]: 0 2.Start Delay Compr sec. [0-1800]: 20 3.Open Delay Valve sec. [0-1800]: 0 4.Stop Delay Fan sec. [0-1800]: 0 5.Stop Delay Compr sec. [0-1800]: 0 6.Valve Active Duration sec. [0-1800]: 20 7.Ice Build start tempr. [float]: 3.0 8.De-ice Exit Tempr. [float]: 5.0 9.Ice build up Duration (sec.) [0-1800]: 1500 10.De-ice Duration (sec.) [0-1800]: 600 11.De-ice Dis/Active/Passive [0/1/2]: 2 12.High Pressure Dis/Ena [HPd][0/1]: 1 13.High Pressure Temp. [HPt][float]: 50.0 14.Low Pressure Dis/Ena [LPd][0/1]: 1 15.Low pressure delta Tempr. [LPt][float]: 5.0 16.Set Value [float]: 50.0 17.Set Value hysterisis []: 4.0 18.Night Max Fan Speed Rpm % [0-100]: 50 19.Night SetPoint Value Offset [0]: 0 20.Fan Operation Mode [0/1/2]: 0 21.Auto Flow [0/1]: 1 22.Fresh Air in [0/1]: 1 -------------------------------------------------------------